1KVA Transformer
ELECTRON FREQUENCY CONVERTER
60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
Solid State Frequency Converter Specifications
Model | 1.5KSS6050/5060 |
Capacity | 1.5KVA/1050W |
Input | |
Voltage | 120 or 220V |
Voltage Range | 120V-15%/+20% or 220V-15%/+20% |
Current
Requirement |
220V – 7.8A @ Full Load (11.8A @ Current limit) |
120V – 14.4A @ Full Load (21.6A @ Current limit) | |
Frequency | Any Frequency from 45 – 65 hz (specify if 400hz) |
Phase | Single |
Output | |
Voltage | 120 or 220Vac ±20% Adjustable from nominal |
Voltage Regulation | ±1% From setpoint |
Frequency | 50Hz or 60Hz (selectable with switch) |
Frequency Regulation | ±.0005 Hz |
Harmonic Distortion | < 3% at 100% Linear Load |
Output Waveform | Pure Sinewave |
Output Current @ .7pf | 220V-6.8A |
120V-12.5A | |
Non-Linear Peak Current for 30 sec. | 220V-10.2A |
120V-18.8A | |
Power Factor | 0.7 |
Efficiency | |
AC to AC | >85% |
Protection | |
Overload Capacity | 110% continuous, 110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of overload. |
Short Circuit | Unit will cut out and must be manually restarted |
EMI Filter | 10-100KHz at 40dB, 100KHz-100MHz at 70dB (CE Approved) |
Over Temperature | Inverter auto cut-off when heat sink temp. over 80° C |
Audible Alarm | |
Overload | Sounds continuously |
Converter Fault | Sounds continuously |
Indicator | |
LCD | Converter status, INPUT & OUTPUT voltage-frequency, loading % |
LED | Line(Utility Power On): Green LED Fault: Red LED
Inverter(Converter Power Output): Green LED Overload: Yellow LED |
Environment | |
Operation Temp. | 0-40° C; 32-104° F |
Relative Humidity | 20-90% non-condensing |
Audible Noise | < 45dB |
Physical | |
Net Weight |
144lbs/64.8kg |
Dimension | |
Depth |
21 3/8in/54.2cm |
Width |
7 1/8in/18.1cm |
Height |
19 3/8in/49.3cm |