ELECTRON FREQUENCY CONVERTER

60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
8KVA Converter
8KVA Solid State Frequency Converter Specifications
Model 8KSS 6050/5060
Capacity 8KVA/6.4KW
Input
Voltage 120 or 220V-15%/+20%
Current

Requirement

220V – 41.8A @ Full Load (62.7A @ Current limit)
120V – 76.7A @ Full Load (115A @ Current limit)
Frequency Any Frequency from 45 65 hz (specify if
400hz)
Phase Single
Output
Voltage 120 or 220Vac ±20% Adjustable from nominal
Voltage Regulation ±1% From setpoint
Frequency 50Hz or 60Hz (Switch selectable) (400
Hz available)
Output Waveform Pure Sinewave
Voltage Regulation ±1%
Frequency Stability ±0.0005Hz
Transient Response ± 3% (100% Load Variance) No load to full
load with full

recovery within 5 cycles

Waveform Sinewave THD < 3% at 0-100% linear
load
Output Current @ .8pf 220V – 36.4A
120V – 66.7A
Overload@150%

for 30 seconds

220V – 54.6A
120V – 100.1A
Efficiency
AC to AC >85%
Power Factor 0.8
Crest Ratio 3:1
Protection
Overload 150% 30 second cut off (Current Limited)
Overload Capacity 110% continuous, 110-150% load 30 seconds,
over 150%

causes unit to shut down. Auto restart upon removal of the

overload.

Short Circuit Unit will cut-off and must be manually
restarted
EMI Filter 10-100KHz at 40dB; 100KHz-100MHz at 70dB
Audible Alarm
Overload Sounds continuously
Fault Sounds continuously
Indicator
LCD Converter status, I/P & O/P voltage,
I/P & O/P frequency
LED
Line: Green LED Inverter: Green LED
Fault: Red LED Overload: Yellow LED
Environment
Operation Temperature 0-40° C; 32-104° F
Relative Humidity 20-90% (non-condensing)
Audible Noise < 58dB (at 1 meter)
Physical
Input Terminal Block
Output Terminal Block (worldwide outlets available)
Net Weight 366lbs/166.4kg
Width 18.9in/48cm
Depth 13.6in/34.5cm
Height 34in/88.64 on wheels
Which Design?