1KVA Converter
ELECTRON FREQUENCY CONVERTER
60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
Solid State Frequency Converter Specifications 400Hz
| Model | 1KSS60400/50400 | ||||
| Capacity | 1KVA/700W | ||||
| Input | |||||
| Voltage | 120V or 220V *see note | ||||
| Voltage Range | 120V -15%/+20% or 220V -15%/+20% | ||||
| Current
Requirement |
220V – 5.2A @ Full Load (7.8A @ Current limit) | ||||
| 120V – 9.6A @ Full Load (14.3A @ Current limit) | |||||
| Frequency | 50Hz or 60Hz | ||||
| Phase | Single | ||||
| Output | |||||
| Voltage | 115V (Locked) | ||||
| Voltage Regulation | ±1% | ||||
| Frequency | 400Hz | ||||
| Frequency Regulation | ±0.016Hz (Xtal oscillator) | ||||
| Harmonic Distortion | <3% at 100% linear load | ||||
| Output Waveform | Pure Sinewave | ||||
| Output Current @ .7pf | 220V – 4.5A | ||||
| 120V – 8.3A | |||||
| Non-Linear Peak
Current for 30 sec. |
220V – 6.8A | ||||
| 120V – 12.5A | |||||
| Power Factor | 0.9 | ||||
| Efficiency | |||||
| AC to AC | >85% | ||||
| Overload Capacity | 110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload. |
||||
| Short Circuit | Unit will cut off and must be manually restarted | ||||
| EMI Filter | 10-100KHz at 40dB, 100KHz-100MHz at 70dB | ||||
| Over Temperature | Inverter auto cut-off when heat sink temp over 80ºC | ||||
| Audible Alarm | |||||
| Overload | Sounds continuously | ||||
| Converter Fault | Sounds continuously | ||||
| Indicator | |||||
| LCD | Converter status, Input & Output voltage – frequency, loading % | ||||
| LED |
|
||||
| Environment | |||||
| OperationTemp. | 0-40° C; 32-104° F | ||||
| Relative Humidity | 20-90% non-condensing | ||||
| Audible Noise | Less than 45dB (at 1 meter) | ||||
| Physical | |||||
| Net Weight | 67.5lbs/30.7kg | ||||
| Width | 7 1/8in/18.1cm | ||||
| Depth | 16in/40.6cm | ||||
| Height | 19 3/8in/49.3cm | ||||
| Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line) – with 2 hot lines and 240V single phase (from a 120/20V split-phase source) – 2 hot lines are both acceptable with one hot on the input N ternimal, and another hot on the L2 input terminal. | |||||