1KVA 220v 50Hz to 120v 60Hz Converter
ELECTRON FREQUENCY CONVERTER
60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
Solid State Frequency Converter Specifications
Model | 1KSS6050/5060 | ||||
Capacity | 1KVA/700W | ||||
Input | |||||
Voltage | 120 or 220V | ||||
Voltage Range | 120V-15%/+20% or 220V-15%/+20% | ||||
Current
Requirement |
220V – 5.2A @ Full Load (7.8A @ Current limit) | ||||
120V – 9.6A @ Full Load (14.3A @ Current limit) | |||||
Frequency | Any Frequency from 45 65 hz (specify if 400hz) | ||||
Phase | Single | ||||
Output | |||||
Voltage | 120 or 220Vac ±20% Adjustable from nominal | ||||
Voltage Regulation | ±1% From setpoint | ||||
Frequency | 50Hz or 60Hz (Switch selectable) (400Hz available) | ||||
Frequency Regulation | ±.0005 Hz | ||||
Harmonic Distortion | < 3% at 100% Linear Load | ||||
Output Waveform | Pure Sinewave | ||||
Output Current @ .7pf | 220V – 4.5A | ||||
120V – 8.3A | |||||
Non-Linear Peak
Current for 30 sec. |
220V – 6.8A | ||||
120V – 12.5A | |||||
Power Factor | 0.7 | ||||
Efficiency | |||||
AC to AC | >85% | ||||
Protection | |||||
Overload Capacity | 105% continuous, over 105% causes unit to shut down. Auto restart upon removal of overload. | ||||
Short Circuit | Unit will cut out and must be manually restarted | ||||
EMI Filter | 10-100KHz at 40dB, 100KHz-100MHz at 70dB (EN 50091-2 CE approved) | ||||
Over Temperature | Inverter auto cut-off when heat sink temp. over 80° C | ||||
Audible Alarm | |||||
Overload | Sounds continuously | ||||
Converter Fault | Sounds continuously | ||||
Indicator | |||||
LCD | Converter status, INPUT & OUTPUT voltage-frequency, loading % | ||||
LED |
|
||||
Environment | |||||
Operation Temp. | 0-40° C; 32-104° F | ||||
Relative Humidity | 20-90% non-condensing | ||||
Audible Noise | < 45dB @ 3 ft. | ||||
Physical | |||||
Net Weight |
67.5lbs/ 30.7kg |
||||
Dimension | |||||
Depth |
16in/ 40.6cm |
||||
Width |
7.1in/ 18cm |
||||
Height |
12.1in/ 30.73cm |