30KSS36050/5060
ELECTRON FREQUENCY CONVERTER
60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
30KSS36050/5060
| VISICOMM INDUSTRIES KSS3 SERIES FREQUENCY CONVERTERS  | 
||
|---|---|---|
| PHASE | 3-Phase input / 3-Phase Output | |
| MODEL | 30KSS36050/5060 | |
| CERTIFICATION | UL STD 1778 / CSA STD C22.2no107.305  | 
|
| INPUT | ||
| INPUT VOLTAGE (Specify) | 208VY / 380VY / 400VY / 415VY or 220VΔ / 380VΔ / 460VΔ  | 
|
| INPUT RANGE | All above are nominal input voltages, and can vary ±20%  | 
|
| INPUT FREQUENCY (Specify) | 50 / 60 Hz ±7% | |
| POWER WALK IN | 0% – 100% : 20 SECONDS | |
| OUTPUT | ||
| OUTPUT VOLTAGE (Specify) | 208VY / 380VY / 400VY / 415VY or 220VΔ / 380VΔ / 460VΔ  | 
|
| For 50hz output, we recommend 230/400V wye 4 wire (Adjustable ±10%), the common market standard, to duplicate both the continental 220/380V 4 wire standard, and the British 240/415V 4 wire standard.  | 
||
| All above are nominal output voltages, and adjustable by potentiometer by ±10%  | 
||
| VOLTAGE REGULATION | ±1% of settings | |
| WAVEFORM | SINEWAVE | |
| OUTPUT and POWER FACTOR | 30KVA @ 0.8 | |
| OUTPUT FREQUENCY (Specify) | 50 or 60 Hz ± 0.05 Hz | |
| PHASE SHIFT UNDER 100% UNBALANCE LOAD  | 
<0.5º | |
| THD (LINEAR LOAD) | <2% | |
| CREST FACTOR | 3:1 | |
| OVERLOAD | <100% | CONTINUOUS | 
| 110-125% | 15 MINUTES | |
| 125-150% | 10 MINUTES | |
| >150% | 1 MINUTE | |
| OVERALL CHARACTERISTICS  | 
||
| OVERAL EFFICIENCY | 91% | |
| MAXIMUM HEAT DISSIPATION (KW)  | 
1.9 | |
| DIMENSIONS (H x W x D) mm / in | 1450 x 550 x 1000 / 58 x 22 x 40 | |
| WGT. KG/lbs | 400 / 884 | |