6.25KVA Converter
ELECTRON FREQUENCY CONVERTER
60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz
Solid State Frequency Converter Specifications
Model | 6.25KSS 6050/5060 | ||||
Capacity | 6.25KVA/5KW | ||||
Input | |||||
Voltage | 120 or 220V-15%/+20% | ||||
Voltage Range | -15%/+20% | ||||
Current
Requirement |
220V – 32.7A @ Full Load (49A @ Current limit) | ||||
120V – 59.9A @ Full Load (90A @ Current limit) | |||||
Frequency | Any Frequency from 45 65 hz (specify if 400hz) | ||||
Phase | Single | ||||
Output | |||||
Voltage | 120 or 220Vac ±20% Adjustable from nominal | ||||
Voltage Regulation | ±1% From setpoint | ||||
Frequency | 50Hz or 60Hz (Switch selectable) (400Hz available) | ||||
Frequency Regulation | ±0.0005Hz | ||||
Harmonic Distortion | < 3% at 100% Linear Load | ||||
Output Waveform | Pure Sinewave | ||||
Output Current @ .8pf | 220V – 28A | ||||
120V – 52.1A | |||||
Overload@150% for 30 seconds | 220V – 42A | ||||
120V – 78.2A | |||||
Efficiency | |||||
AC to AC | >85% | ||||
Power Factor | 0.8 | ||||
Crest Factor | 3:1 | ||||
Indicator-Detachable & Remote Control | |||||
LCD | Automatically configures to monitor voltage, frequency, and loading, simultaneously. |
||||
LED |
|
||||
Audible Alarm | |||||
Overload | Continuously beeping | ||||
Fault | Continuously beeping | ||||
Protection | |||||
Overload | 150% Delay 30 seconds, current limited | ||||
Short Circuit | Current limited and cut-off, fuse and breaker | ||||
EMI Filter | 10-100KHz at 40dB; 100KHz-100MHz at 70dB | ||||
Over Temperature | Inverter auto cut-off when heat sink temp. over 80 ° C | ||||
Dimension | |||||
Depth | 22.9in/58.2cm | ||||
Width | 9.63in/24.5cmcm | ||||
Height | 27.75in/70.5cm | ||||
Environment | |||||
Operation Temperature | 0-40° C; 32-104° F | ||||
Relative Humidity | 20-90% (non-condensing) | ||||
Noise Level | < 58dB (at 1 meter) | ||||
Weight | |||||
LBS/KG | 232lbs/105.5kg on wheels |