Solid State Frequency Converter Specifications 400Hz
| Model | 5KSS60400/50400 | ||||
| Capacity | 5KVA/4KW | ||||
| Input | |||||
| Voltage | 120V or 220V *see note | ||||
| Voltage Range | -15%/+20% | ||||
| Current
Requirement |
220V – 26.1A @ Full Load (39.2A @ Current limit) | ||||
| 120V – 47.9A @ Full Load (71.9A @ Current limit) | |||||
| Frequency | 50Hz or 60Hz ±5% | ||||
| Phase | Single | ||||
| Output | |||||
| Voltage | 115V (Locked) | ||||
| Voltage Regulation | ±1% | ||||
| Frequency | 400Hz | ||||
| Frequency Regulation | ±0.016Hz (Xtal oscillator) | ||||
| Harmonic Distortion | <3% (100% linear load.) | ||||
| Output Waveform | Pure Sinewave | ||||
| Output Current @ .8pf | 220V – 22.7A | ||||
| 120V – 41.7A | |||||
| Overload@150% for 30 seconds | 220V – 34.1A | ||||
| 120V – 61.5A | |||||
| Efficiency | |||||
| AC to AC | >85% | ||||
| Power Factor | 0.8 | ||||
| Crest Ratio | 3:1 | ||||
| Indicator- Detachable& Remote Control |
|||||
| LCD | Automatically configures to monitor voltage, frequency and loading, simultaneously. | ||||
| LED |
|
||||
| Audible Alarm | |||||
| Overload | Continuously beeping | ||||
| Fault | Continuously beeping | ||||
| Protection | |||||
| Overload | 150% delay 30 seconds, current limited | ||||
| Short Circuit | Current limited cut-off, fuse and breaker | ||||
| EMI filter | 10-100KHz at 40dB; 100KHz-100MHz at 70dB | ||||
| Over Temperature | Inverter auto cut-off when heatsink temp. over 80ºC | ||||
| Dimension | |||||
| Depth | 22.9in/58cm | ||||
| Width | 9.63in/24.5cm | ||||
| Height | 27.75in/70.5cm | ||||
| Environment | |||||
| Operation Temperature | 0-40° C; 32-104° F | ||||
| Relative Humidity | 20-90% (non-condensing) | ||||
| Noise Level | < 58dB (at 1 meter) | ||||
| Weight | |||||
| LBS/KG | 232lbs/105.5kg (on wheels) | ||||
| Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line) – with 2 hot lines and 240V single phase (from a 120/20V split-phase source) – 2 hot lines are both acceptable with one hot on the input N ternimal, and another hot on the L2 input terminal. | |||||