Single Phase Frequency Converters 50/60 Hz
18 models 1KVA to 20KVA
50 or 60hz input,
50hz or 60hz output
Single Phase Frequency Converters 400hz
18 models 1KVA to 20KVA
50hz or 60hz input and
400hz output
Three Phase Solid State Frequency Converters
50 or 60 Hz
57 models 10 to 320KVA
Three Phase Solid State Frequency Converters
400hz
57 models 10 to 320KVA
Solid State Design Considerations Manuals and Connection Diagrams Accessories
Outdoor Enclosures, Carts,
Distribution Panels etc.
Application
Notes and Photos
solid state frequency converter
rotary frequency converter
Rotary 1 or 3 Phase Frequency Converters
50 or 60hz output
6KVA to 2000KVA
Rotary 400Hz output Frequency Converters
1 or 3phase
10KVA to 250 KVA
Rotary Frequency Converters Accessories
Enclosures (Indoor quietized and Outdoor) Digital Meters, RS232 and Data Logging, etc.
Rotary Design Considerations Starting Surge of motors in the load, Large SCR loads, power factor and resistive loads, Operating Noise Level.
Rotary Application Notes and Photos Operating Noise and solutions to this problem Line Isolation Sets
  Visicomm Industries Company Profile Contact Us Site Map
Solid State Frequency ConverterRotary Frequency Converter
solid state frequency converter rotary frequency converter

Electrocon Frequency Converters

60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz

1.25KVA Solid State Frequency Converter Specifications

 
which frequency converter design
which size frequency converter
buy or rent frequency converter

Printer Friendly Version

Model 1.25KSS6050/5060
Input
Input Voltage 100-220VAC
Single Phase 2-Wire
Input Current 20A AC Max. @ Lowest input voltage
Input Power 1725VA
Input Frequency 45-60Hz
Holdup Time 20 milli-seconds
Output
Output Voltage Selectable: 100, 115, 220, 230 or 240 VAC
Single Phase 2- Wire
Nominal Output Voltage Scalable by ±10%
Voltage Regulation ±2% of setting
Waveform SINEWAVE
Output Frequency 50 or 60 Hz (±1%)
Nominal Output Frequency,
User selectable offset feature by ± 3Hz from nominal
Power 1.25kVa
THD (Linear Load) Less Than 2%
OverloadLow Range
High Range
33A pk (@120V)
16.5A pk (@240V)
Overall Characteristics
Protection Input fused 20A, Output over-current (thermal)
Dimensions
(H x W x D)
8.50”(21.6cm) X 8.74”( 22.2cm) X 18.0”(45.7cm)
Weight LBS/KG 30 lb/13.6kg
Operating Temperature Range 0 TO 40 degrees Celsius
(Forced air cooling rear/sides)

Specifications subject to change without notice.